摘要
通过某抽水蓄能电站在静止变频器改造过程中出现的保护跳闸事件进行分析,查找出该事件为保护跳闸回路长电缆分布电容较大所引起,同时提出针对性的防范措施以保障设备安全稳定运行。
By analysis on a protection trip event during the transformation of a static frequency converter in a pumped storage power station,it is find out that the event is caused by the large distributed capacitance of the long cables of the trip circuit,and the corresponding preventive measures are proposed to ensure the safe and stable operation of the equipment.
作者
王永卫
杨艳平
梁绍泉
WANG Yongwei;YANG Yanping;LIANG Shaoquan(Shandong Taishan Pumped Storage Power Station Co.,Ltd.,Taian 271000)
出处
《电力安全技术》
2023年第6期29-31,共3页
Electric Safety Technology
关键词
抽水蓄能电站
长电缆
分布电容
保护误动
pumped storage power station
long cable
distributed capacitance
protection mal-operation