换流站TILP型交流滤波器电容器接线柱发热分析研究 被引量:1

Study on Heating Analysis of TILP AC Filter Capacitor Terminals in Converter Station
下载PDF
导出
摘要 研究±500 kV换流站TILP型交流滤波器电容器接线柱频繁发热原因,提出具体的预防解决措施。本文研究新型特殊线夹,为该型设备能够继续良好的运行提供了有力技术支持。通过对不同措施方案进行测试分析和数据研究,对比目前运行情况,得出TILP型交流滤波器电容器频繁发热是由于接线柱结构设计不合理供导流的接触面过小且接触面容易氧化引起,介绍了解决该问题的方案。 The reasons for the frequent heating of the TILP type AC filter capacitor terminals at±500 kV converter station are studied,and specific preventive measures are proposed.In this paper,the new type special wire clips are studied to provide great support to the perfect operation of the equipment.Throughout the test,analysis and data study of different measurements and proposals and comparison with the present operation,it is concluded that the frequent heating of type TILP AC filter capacitor is due to unreasonable design of the structure of the wiring terminal,small surface for current conduction and easy oxidization of the contacting surface.The solution for solving the problem is introduced.
作者 马虎涛 吴永利 申廷进 许业芳 吴秀荣 贲为勇 梁明纯 黄楚秋 MA Hutao;WU Yongli;SHEN Tingjin;XU Yefang;WU Xiurong;BI Weiyong;LIANG Mingchun;HUANG Chuqiu(CSG EHV Power Transmission Company,Tianshengqiao Bureau,Guizhou Xingyi 562400,China;Guilin Power Capacitor Co.,Ltd.,Guangxi Guilin 541004,China)
出处 《电力电容器与无功补偿》 2023年第4期1-4,11,共5页 Power Capacitor & Reactive Power Compensation
基金 中央引导地方专项(桂科ZY20111014) 桂林市重点研发计划项目(20210209-1)。
关键词 电容器 发热 线夹 接触面 capacitor heating wire clips contact surface