机房专用蒸发式冷气机在渭南某C类电信机房的应用

Application of Evaporative Air Conditioner for Computer Room in a Class C Telecommunications Computer Room in Weinan
下载PDF
导出
摘要 针对渭南市某电信机房空调系统节能改造要求,提出节能、环保的蒸发冷却技术,采用机房专用蒸发式冷气机对机房空调系统进行节能降温设计。为验证其降温效果是否满足C类机房的温湿度要求,测试其运行时温度和相对湿度,并进行分析,测试结果显示,机房内的平均温度波动范围为26.6℃~28.1℃,平均相对湿度波动范围为49.7%~51.6%,满足C类机房温湿度要求;通过全年运行能耗和经济性分析,得改造后蒸发冷却空调系统年节省电量39837.4kWh,节省电费19918.7元,节能率高达54.1%,其投资回报周期也只有4.3年。 Aiming at the energy-saving transformation requirements of the air-conditioning system of a telecommunications computer room in Weinan City,an energy-saving and environmentally friendly evaporative cooling technology is proposed,and the special evaporative air conditioner in the computer room is used to carry out energy-saving and cooling design for the air-conditioning system of the computer room.In order to verify whether the cooling effect meets the temperature and humidity requirements of the class C computer room,test its operating temperature and relative humidity,and analyze,the test results show that the average temperature fluctuation range in the computer room is 26.6℃~28.1℃,and the average relative humidity fluctuation range is 49.7%~51.6%,which meets the temperature and humidity requirements of the class C computer room;Through the annual operation energy consumption and economic analysis,the evaporative cooling air conditioning system after the renovation saves 39837.4kWh of electricity per year,saves RMB 19,918.7 in electricity costs,saves 54.1%of energy saving rate,and its return on investment period is only 4.3 years.
作者 张振鹏 强天伟 李东林 王秀 Zhang Zhenpeng;Qiang Tianwei;Li Donglin;Wang Xiu(Xi'an Polytechnic University,Xi'an,710048)
机构地区 西安工程大学
出处 《制冷与空调(四川)》 2023年第4期556-561,共6页 Refrigeration and Air Conditioning
关键词 蒸发冷却 机房专用蒸发式冷气机 节能降温 运行能耗 节能率 投资回报周期 evaporative cooling Evaporative air conditioner for machine room Energy saving and cooling operating energy consumption Energy saving rate payback cycle
  • 相关文献

参考文献7

二级参考文献33

  • 1陈沛霖.蒸发冷却技术在非干燥地区的应用[J].暖通空调,1995,25(4):3-8. 被引量:46
  • 2黄翔.国内外蒸发冷却空调技术研究进展(1)[J].暖通空调,2007,37(2):24-30. 被引量:161
  • 3中国气象局气象信息气象资料室,清华大学建筑科技科学系.中国建筑热环境分析专用气象数据集[M].北京:中国建筑工业出版社,2005.
  • 4YD/T1821-2008,通信中心机房环境条件要求[S].北京:中国标准出版社.2008.
  • 5GB/T50174-2008,电子信息系统机房设计规范[S].北京:中国计划出版社,2009.
  • 6澳蓝(福建)实业有限公司.通信机房专用冷气机产品说明书[EB/OL].http://www.aolanchina.com/UpFile/image/pdf/tx05.pdf.
  • 7EcoCooling. Evaporative cooling case study cooling cambridge university data eentre[EB/OL] . [ 2012- 11 - 13]. http: // www. ecocooling, co. uk/ dataeasestudy/cambridge, php.
  • 8ASHRAE.数据处理环境热指南[M].2版.沈添鸿,杨国荣,陈巍,等,译.北京:中国建筑工业出版社,2010.
  • 9Montoya. Sematech electrostatic discharge impact and control worshop [M]//ASHRAE TC 9. 9. 数据处理环境热指南.北京:中国建筑工业出版社,2010:46.
  • 10ASHRAE. ASHRAE environmental guidelines for datacom equipment 2011[M]//数据中心机房空调系统技术白皮书,2011:11.

共引文献24

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部