半封螺杆变频盐水机组节能分析及验证

Energy Saving Analysis and Verification of Semi-Hermetic Screw Brine Unit with VSD
下载PDF
导出
摘要 根据江森自控变频盐水机组的设计及应用特点,分析其部分负荷性能的影响因素。变转速控制压缩机实现部分负荷下仍具有高的绝热效率,经济器也可以始终保持运行,从而克服滑阀调节机组存在的缺点,保证机组在部分负荷下高效率运行。经过实际测试验证,变转速控制的部分负荷性能优势明显。另外,测试过程中,发现污垢系数对机组性能影响显著,在设计过程中需要特别考虑。 According to the design and application features of Johnson Control VSD brine unit,the influencing factors of partial load performance was analyzed.The variable speed control compressor can keep the high adiabatic efficiency in partial load with the economizer operation,so VSD unit can overcome the shortcomings of the slide valve regulating unit and ensure the high efficiency of the unit in partial load.The actual test proved that the variable speed control has the obvious advantages in partial load performance.In addition,per the testing report,it is found that the foul factor has a significant impact on the performance of brine chiller,which need special consideration in the design stage.
作者 陈芳旭 屠永华 奚晔 Chen Fangxu;Tu Yonghua;Xi Ye(IR-ASIA,YORK(Wuxi)Air Conditioning and Refrigeration Co.Ltd.,Wuxi,214111,China)
出处 《冷藏技术》 2023年第3期9-12,共4页 Journal of Refrigeration Technology
关键词 盐水机组 部分负荷性能 变频 经济器 污垢系数 brine chiller partial load performance inverter economize fouling factor
  • 相关文献

参考文献3

二级参考文献21

  • 1伏龙,丁国良,张春路,苏祖坚.螺杆式冷水机组稳态仿真模型的开发与应用[J].暖通空调,2005,35(5):71-75. 被引量:9
  • 2郑祖义,彦启森.中压进气口位置对带经济器螺杆机性能的影响[J].华中理工大学学报,1995,23(7):6972-6972. 被引量:5
  • 3YORK.约克冷冻公司设备操作维护手册.无锡:2010:1.
  • 4Cho Keumnam, Tae Sang-Jin. Evaporation Heat transfer for R-22 and R-407C refrigerant-oil mixture in a microfin tube with a U-bend[J]. International Journal of Refrigeratioga-Revue Intemationale du Froid, 20(10, 23 ( 3 ) : 219-231.
  • 5Ha S, Bergles A E. Influence of oil on local evaporation heat la-ansfer inside a horizontal microfin tube [ J ].ASHRAE Transactions, 1993,99( ptl ) : 1244-1258.
  • 6Hambraeus Katarina. Heat transfer coefficient during twophase flow boiling of HFC-134a[J]. International Journal of Refrigeration-Revue Internationale du Froid, 1991, 14(6) : 357-362.
  • 7Hambraeus K, M Sc. Heat transfer coefficient, two-phase flow boiling of HFC134a [ A ]. International refrigeration conference at Purdue[C]. 1992, : 205-214.
  • 8Hambraeus K. Heat transfer of oil-contaminated HFC134a in a horizontal evaporator[ J]. International Journal of Refrigeration-Revue Intemationale du Froid, 1995, 18 (2):87-99.
  • 9Manwell S P, Bergles A E. Gas-liquid flow patterns in refrigerant-oil mixtures [ J]. ASHRAE Transactions, 1994,100(pt 2):456-464.
  • 10Nidegger Eric, Thome John R, Favrat Daniel. Flow boiling and pressure drop measurements for R-134a/oil mixtures Part 1: evaporation in a microfin tube [ J ].ASHRAE Transactions, 1997,103 (pt 2) : 334.

共引文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部