摘要
Direct air capture(DAC)is one of the most potential technologies to mitigate CO_(2) emission.Adsorption technol-ogy is recognized as a promising CO_(2) capture method in view of its desirable characteristics including reusability of adsorbents and low capital investment.To further improve thermal performance,evaporation/condensation heat of vapor compression refrigeration(VCR)cycle in air condition system of buildings is adopted for adsorp-tion/desorption process of DAC.Thermal performance of a 4-step temperature swing adsorption process(TSA)is analyzed at various adsorption/desorption temperatures by using different adsorbents.Analysis on Coefficient of Performance(COP)of VCR cycle is also conducted in search for a balance between adsorbent and refrigerant.Taking both real working capacity and COP into consideration,Mg-MOF-74&R134a is the best choice for more amounts of CO_(2).Real working capacity of Mg-MOF-74 is up to 0.38 mol•kg−1 at 70°C,which is twice as much as that of zeolite 13X.While zeolite 13X&R134a shows the best performance of two cycles in view of exergy efficiency and COP,which could reach 81.9%and 7.21,respectively,at 35°C.These matches will provide some guidelines for the practical application of the combination of DAC with heating,ventilation and air conditioning(HVAC).
基金
This research was supported by National Natural Science Foundation of China under contract number(51976178).