期刊文献+

一起110千伏油浸式电流互感器电容量异常问题的原因分析 被引量:1

Cause Analysis of Abnormal Capacitance of 110kV Oil Immersed Current Transformer
下载PDF
导出
摘要 针对一起油浸式电流互感器电容量增大的案例,通过显著性差异分析识别了故障,经试验、解体分析查明了异常原因为末屏引出至二次接线盒的压接点存在松动缺陷。该案例的分析对电容式电流互感器电容量异常的分析和处置具有一定借鉴意义。 In view of a case fo increasing capacitance of oil immersed current transformer,that fault is identified significant difference analysis.Through test and disassembly analysis,it is found that the abnormal reason is that the crimping contact from the end screen to the secondary junction box is loose.The analysis of this case has certain reference significance for the analysis and disposal of abnormal capacitance of capacitive current transformer.
作者 石惠承 汪泽州 孙鹏 陈湘如 沈伟 SHI Hui-cheng;WANG Ze-zhou;SUN Peng;CHEN Xiang-ru;SHEN Wei(State Grid Jiaxing Power Supply Company,Jiaxing 314000,China;State Grid Haiyan Power Supply Company,Jiaxing 314000,China;Baoding Jinkehui Electronics Co.Ltd.,Baoding 071000,China;Jiaxing Hengguang Electric Power Construction Co.Ltd.,Engineering Service Branch,Jiaxing 314000,China)
出处 《电气开关》 2023年第5期107-109,113,共4页 Electric Switchgear
关键词 电流互感器 末屏 电容量 显著性差异 current transformer end screen capacitance significance