针对某机场两轮扩能后候机楼两个独立制冷站共同为候机楼供给冷源,存在安全冗余度低、能耗浪费等问题,采取增加集水器、管路拆改、改变水流方向等措施,最终达到了预期效果。
In view of the problems of low safety redundancy and waste of energy,two independent refrigeration stations in the terminal building of an airport jointly supply cold source after two-round capacity expansion,measures such as adding water collectors,removing pipelines and changing the direction of water flow have finally achieved the expected effect.
作者
熊德湧
XIONG Deyong(Xiamen Zhaoxiang Property Service Co.,Ltd.,Fuzhou Branch,Fuzhou 350000)
出处
《现代制造技术与装备》
2023年第10期106-108,共3页
Modern Manufacturing Technology and Equipment
关键词
制冷站
连通运行改造
调试运行
候机楼
refrigeration station
connected operation reform
debugging and running
terminal building