期刊文献+

A positive-sequence current based directional relaying approach for CCVT subsidence transient condition 被引量:1

原文传递
导出
摘要 In this work,a directional relaying algorithm is proposed for transmission line to prevent relay maloperation during coupling capacitor voltage transformer(CCVT)subsidence transient.The effect of CCVT subsidence transient during single-pole-tripping condition is highlighted in this paper.The proposed method which is based on phase angle difference of post fault and prefault positive sequence current can help the directional relay to take accurate decision during erroneous CCVT secondary response.The available CCVT model in PSCAD is not able to generate significant subsidence transient in the secondary side.So,a new CCVT model is developed in EMTDC/PSCAD domain for transient response analysis and to check the relay operation.Next,the performance of different voltage and current information based directional relaying techniques have been analyzed and compared with the proposed method.The results are evaluated for different system and fault conditions.Results demonstrate the accuracy of the proposed method.
出处 《Protection and Control of Modern Power Systems》 2017年第1期81-91,共11页 现代电力系统保护与控制(英文)
  • 相关文献

同被引文献16

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部