摘要
GB 51251-2017《建筑防烟排烟系统技术标准》对设置在吊顶内的排烟风管的隔热层提出了要求,且明确了隔热层厚度不小于40 mm,但规范并未明确隔热材料的导热系数等热物性参数。本文讨论和分析了隔热层、复合包覆风管的隔热性及耐火极限等,为设计、审查、验收提供参考。
Technical standard for smoke management systems in buildings(GB 51251-2017)puts forward the requirements for the thermal insulation layer of smoke exhaust ducts in suspended ceilings,and clarifies that the thickness of the thermal insulation layer is not less than 40 mm.But the specification does not specify the thermal physical parameters such as the thermal conductivity of the thermal insulation materials.In this paper,the thermal insulation performance and the fire endurance of the thermal insulation layers and the composite clad ducts are discussed and analysed,which provides a reference for design,review and acceptance.
作者
刘付伟
陈焰华
昌爱文
Liu Fuwei;Chen Yanhua;Chang Aiwen(CITIC General Institute of Architectural Design and Research Co.,Ltd.,Wuhan)
出处
《暖通空调》
2023年第12期104-107,166,共5页
Heating Ventilating & Air Conditioning
关键词
排烟风管
隔热层
隔热性
导热系数
耐火极限
smoke exhaust duct
thermal insulation layer
thermal insulation performance
thermal conductivity
fire endurance