500kV变压器中压套管故障分析

Fault Analysis of Medium Pressure Bushing of 500kV Transformer after Moisture
下载PDF
导出
摘要 某500kV变电站主变中压侧套管油中部分发生接地故障,电弧放电产生大量气体,导致本体鼓包变形。本文中作者对变压器进行内检及套管解体检查,结合油色谱诊断试验和故障录波分析,判断此次套管故障的主要原因为套管进水受潮和下瓷套有质量缺陷。 Grounding fault occurs in the middle of casing oil of middle pressure side of main transformer in a 50okV substation.Arc discharge produces a lot of gas,which causes bulk bulge distortion.The main reason for the failure of the transformer casing is that the water inlet of the casing is wet and the lower ceramic sleeve is defective.Based on the wet condition of transformer medium pressure bushing,further requirements are put forward to manufacturers and maintenance personnel to avoid the recurrence of similar failures.
作者 李世泽 张云 张亮 赵腾飞 陈少帅 蒲园园 LI Shi-ze;ZHANG Yun;ZHANG Liang;ZHAO Teng-fei;CHEN Shao-shuai;PU Yuan-yuan(State Grid Hebei Extra High Voltage Company,Shijiazhuang 050071,China)
出处 《变压器》 2023年第11期64-67,共4页 Transformer
关键词 变压器 中压套管 故障录波 故障分析 Transformer Medium pressure bushing Fault recording Fault analysis