摘要
在运行状态下,油中溶解气体组分、铁芯和夹件接地电流是判断变压器运行状态的有效方法。为了准确判断油中溶解气体组分、铁芯和夹件接地电流数据异常时变压器的内部状态,以及停电后更精准地定位异常位置和消除异常点,文章详细分析了铁芯和夹件在两点接地和一点接地2种运行方式下出现多点接地异常、油中溶解气体组分异常的各种可能性,并提出了对应的判断和解决异常的方法,最后,基于某110 kV异常变压器进行了试验验证,表明所作分析对判断、消除多点接地问题具有切实意义,具有较高的应用价值和推广价值。
Under operating conditions,dissolved gas components in oil,grounding current of iron cores and clamps are effective methods to determine the operating status of transformers.In order to accurately determine the internal state of transformers when the dissolved gas components in oil and the grounding current data of iron cores and clamps are abnormal,as well as to more accurately locate and eliminate abnormal points after power outage,this article analyzes in detail the various possibilities of multiple grounding abnormalities and dissolved gas components in oil under two operation modes of two point grounding and one point grounding for iron cores and clamps,and proposes corresponding methods for judging and resolving abnormalities,Finally,experimental verification was conducted on a 110 kV abnormal transformer,indicating that the analysis has practical significance in determining and eliminating multi-point grounding problems,and has high application and promotion value.
作者
李飞
焦方军
姜晓东
房悦
杨光
LI Fei;JIAO Fangjun;JIANG Xiaodong;FANG Yue;YANG Guang(State Grid Shandong Zibo Power Supply Company,Shangdong Zibo 255000,China;State Grid Shandong Electric Power Company,Shangdong Jinan 250013,China)
出处
《农村电气化》
2023年第12期20-24,共5页
Rural Electrification
基金
国网山东省电力公司科技项目“变压器铁芯接地电流广域状态感知预警技术研究与应用”(2023A-151)。
关键词
变压器
铁芯和夹件
多点接地
电容量
transformer
iron core and clamps
multi point grounding
capacitance