期刊文献+

一起断路器漏气原因分析

Causal Analysis of a Case of Gase Leakage Encountered by an Actual Circuit Breaker
下载PDF
导出
摘要 针对一起断路器漏气事故,通过对该断路器进行现场停电检查、压力变化统计、解体检测、返厂检测、相关部件试验室检测等测试后,发现断路器瓷套部位存在多处裂纹,最后确定了断路器泄漏原因。 This paper reports a case of gas leakage accident encountered by an actual circuit breaker.It describes the examination process of the circuit breaker including on-site power failure inspection,pressure change statistics,disintegration detection,return-to-manufacturer test,and laboratory test of related components,through which it has been found many cracks in the porcelain bushing part.It finally analyzes the cause of the circuit breaker gas leakage.
作者 李凯 许宏伟 沙莎 李寒煜 初德胜 郑欣 刘荣海 王顺涛 LI Kai;XU Hongwei;SHA Sha;LI Hanyu;CHU Desheng;ZHENG Xin;LIU Ronghai;WANG Shuntao(Yunnan Power Grid Co.,Ltd.,Electric Power Research Institute,Kunming 650217,China;Mechanical Engineering College of North China Electric Power University,Baoding 071003,China)
出处 《电工技术》 2024年第1期152-155,159,共5页 Electric Engineering
关键词 断路器 气体泄漏 瓷套 circuit breaker gas leakage porcelain bushing