磁悬浮冷水机组在节能改造项目中的实测与分析

Measurement and Analysis of Magnetic Levitation Chillers in Energy-saving Renovation Projects
下载PDF
导出
摘要 本文根据空调厂家提供的磁悬浮冷水机组性能参数,评价磁悬浮机组能效水平,机组COP为6,IPLV为11,达到冷水机组国家一级能效标准。对青岛市采用磁悬浮冷水机组进行节能改造的项目进行数据监测,结果表明,机组负荷率和冷却水回水温度对磁悬浮机组效率有明显影响。空调系统控制策略会影响磁悬浮机组的实际运行能效,磁悬浮冷水机组应用在实际项目中,存在建筑负荷供需不匹配,输配系统能耗偏高的问题。提高机房整体能效,需根据建筑的实际情况,合理选用高效设备,并搭配合理的输配系统及控制策略。 This article evaluates the energy efficiency level of the magnetic levitation chiller unit based on the performance parameters provided by the air conditioning manufacturer.The unit has a COP of 6 and an IPLV of 11,meeting the national first-class energy efficiency standard for chillers.The data monitoring of the energy-saving renovation project using magnetic levitation chillers in Qingdao shows that the unit load rate and cooling water return temperature have a significant impact on the efficiency of magnetic levitation chillers.The control strategy of the air conditioning system will affect the actual operational energy efficiency of the magnetic levitation chiller.When the magnetic levitation chiller is applied in practical projects,there is a mismatch between building load supply and demand,and the energy consumption of the transmission and distribution system is relatively high.To improve the overall energy efficiency of the computer room,it is necessary to select efficient equipment reasonably based on the actual situation of the building,and match it with a reasonable transmission and distribution system and control strategy.
出处 《节能与环保》 2023年第12期72-79,共8页
关键词 磁悬浮冷水机组 节能改造 COP EER magnetic levitation chiller energy saving renovation COP EER
  • 相关文献

参考文献6

二级参考文献26

  • 1成勇,倪昀炜.磁悬浮制冷与传统压缩制冷技术比较[J].通信电源技术,2012,29(S1). 被引量:5
  • 2薛志峰,江亿.北京市大型公共建筑用能现状与节能潜力分析[J].暖通空调,2004,34(9):8-10. 被引量:182
  • 3陈晓阳,江亿,李震.湿度独立控制空调系统的工程实践[J].暖通空调,2004,34(11):103-109. 被引量:76
  • 4江亿.我国建筑耗能状况及有效的节能途径[J].暖通空调,2005,35(5):30-40. 被引量:609
  • 5龙惟定.建筑节能与建筑能效管理[M].北京:中国建筑工业出版社,2006.
  • 6江亿.数据中心空调节能[R].北京:中国勘察设计协会建筑与设备分会北京市委员会.2012.
  • 7JAHANGEER K A, ANDREW A O Tay, MD Raisul lslam. Numerical investigation of transfer coefficients of an evap- oratively-cooled condenser[J]. Applied Thermal Engineering, 2011,31 (10) : 1655-1663.
  • 8PONGSAKORN Sarntichartsak,SIRCHAI Thepa. Modeling and experimental study on the performance of an inverter air conditioner using R-410A with evaporatively cooled condenser[J]. Applied Thermal Engineering,2013,51 (S1-2) . 597-610.
  • 9WANG Tianwei,SHENG Chenguang, A G Agwu Nnanna. Experimental investigation of air conditioning system using evaporative cooling condenser[J]. Energy and Buildings, 2014,81 (81) . 435-443.
  • 10LIU H uanwei,ZHOU Qiushu,LIU Yuling,et ah Experimental study on cooling performance of air conditioning sys- tem with dual independent evaporative condenser[J]. International Journal of Refrigeration,2015,55:85-92.

共引文献40

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部