摘要 根据现有的标准规范和安全管控要求,精细化工项目控制室、机柜间不能布置在甲、乙类厂房(车间)和仓库内。灵活配线的电子布线I/O取得防爆认证后,可以直接在甲、乙类车间爆炸危险性气体环境现场安装使用,就近接入仪表信号,但存在诸多不便。设计应采取必要措施,在甲、乙类车间内布置专用的远程仪表间,集中安置控制系统的电子布线I/O机柜。 According to existing codes and standards as well as the safety control requirements,the control room and rack room of fine chemical projects cannot be arranged inside the Class A and Class B buildings (workshops) and warehouses.After obtaining explosion-proof certification for flexible wiring of electronic wiring I/O,it can be directly installed and used in explosive gas environments in Class A and B workshops,and connected to instrument signals nearby,but there are many inconveniences.Necessary measures should be taken in the design to arrange dedicated remote instrument rooms in Class A and B workshops,with centralized placement of electronic wiring I/O cabinets for the control system.
作者 沈奕峰 Shen Yifeng(Zhejiang TITAN Design&Engineering Co.,Ltd.,Hangzhou 310030,China)
出处 《化工设计》 CAS 2024年第1期41-43,50,2,共5页 Chemical Engineering Design
关键词 精细化工 甲类车间 机柜 输入/出 电子布线 远程仪表间 fine chemical industry class A workshop cabinet input/output electronic wiring remote instrument room