摘要 变压器重新投运时,为了快速建立磁场,往往会出现励磁涌流,而变压器剩磁的存在,将进一步加大励磁涌流的幅值,使得变压器的保护误动作。变压器在进行电气试验后,因电气试验施加的直流电流,变压器铁心中的剩磁会进一步增加,对变压器正常投运造成隐患。因此,在变压器投运前对其剩磁的降低或消除,是确保变压器正常投运的因素之一。文章研究一种对变压器剩磁进行检测、具备变压器消磁功能和低压交流剩磁验证功能的消磁仪器,从而提高变压器消磁判断能力及效率。 When the transformer is put into operation again,in order to quickly establish the magnetic field,there will often be an exciting inrush current,and the presence of the transformer's remanence will further increase the amplitude of the excitation inrush current,making the protection of the transformer misoperate.After the electrical test of the transformer,due to the DC current applied in the electrical test,the remanence in the transformer core will further increase,causing hidden dangers to the normal operation of the transformer.Therefore,the reduction or elimination of remanence before the transformer is put into operation is one of the factors to ensure the normal operation of the transformer.This paper mainly studies a degaussing instrument with transformer degaussing function and low voltage AC remanence verification function.The transformer remanence is detected and reduced,so as to improve the transformer degaussing judgment ability and efficiency.
作者 黄继来 刘茂集 刘冲 朱翘楚 魏文力 HUANG Jilai;LIU Maoji;LIU Chong;ZHU Qiaochu;WEI Wenli(Wenzhou Power Supply Company,State Grid Zhejiang Electric Power Co.,Ltd.,Zhejiang Wenzhou 325000,China;Entrepreneurship and Innovation Center,State Grid Zhejiang Electric Power Co.,Ltd.,Zhejiang Hangzhou 310000,China)
出处 《农村电气化》 2024年第4期77-79,共3页 Rural Electrification
基金 国网浙江省电力有限公司双创项目:一种变压器消磁分析仪的研制(B711JZ210010)。
关键词 变压器 励磁涌流 消磁 transformer excitation inrush current degaussing
  • 相关文献

参考文献6

二级参考文献38

  • 1李钷,乌云高娃,刘涤尘,叶念国.Preisach模型剩磁计算与抑制励磁涌流合闸角控制规律[J].电力系统自动化,2006,30(19):37-41. 被引量:32
  • 2中国电力企业家协会供电分会.电气试验与油化验[M].北京:中国电力出版社,1999:88.
  • 3建设部,国家质监总局.电气装置安装工程电气设备交接试验标准[M].北京:中国计划出版社,2006.
  • 4陈化钢.电气设备预防性试验方法技术问答[R].北京:华北电力试验研究院,1992.
  • 5赵凯华,陈熙谋.电磁学[M].北京:高等教育出版社,2011.
  • 6Corrodi Y, Member S, Kamei K, et al. Influence of system transients on the residual flux of an unloaded transformer[C]. IEEE Power and Energy Society General Meeting, 2011: 1-7.
  • 7Wu Yunfei, Hu Huiran, Luo Wei, et al. Research on no-load test of 1000kV ultra-high voltage transformer[C]. IEEE Power and Energy Engineering Conference (APPEEC), 2011: 1-6.
  • 8Taylor D I, Law J D, Johnson B K, et al. Single-phase transformer inrush current reduction using prefluxing[J]. IEEE Transactions on Power Delivery, 2012, 27(1): 245-252.
  • 9Taylor D I, Fischer N, Law J D, et al. Using lab view to measure transformer residual flux for inrush current reduction[C]. IEEE North American Power Symposium(NAPS), 2009: 1-6.
  • 10Chiesa N, Avendano A, Hidalen H K, et al. On the ring down transient of transformers[C]. International Conference on Power Systems Transients(IPST’07) in Lyon, France, 2007.

共引文献47