变电站直流系统接地故障案例分析

Case Analysis of Grounding Fault in Substation DC System
下载PDF
导出
摘要 直流系统是变电站的保障性系统,发生故障时会影响变电站的安全可靠运行,其中直流系统接地占直流系统故障的比例最高。针对直流系统接地故障实例进行分析研究,并结合工作实践经验,探讨了查找和排除直流接地故障的技术方法。 The DC system serves as the guarantee system for substations,and any faults within it can significantly impact the safe and reliable operation of the substation.Among all potential issues,grounding faults in the DC system account for the highest proportion.This paper aims to discuss technical methods for detecting and eliminating such grounding faults based on case analysis,research,and practical experience.
作者 王占颖 杨萌 徐琳 WANG Zhanying;YANG Meng;XU Lin(State Grid Qingpu Power Supply Company,SMEPC,Shanghai 201700,China;Gu'an Power Supply Branch,State Grid Jibei Electric Power Co.,Ltd.,Langfang O65500,Hebei Province,China)
出处 《电力与能源》 2024年第2期186-188,共3页 Power & Energy
关键词 直流系统 接地故障 故障分析 DC system grounding fault fault analysis