计及功率控制型构网变流器接入的交流系统暂态稳定性仿真研究

Simulation study on transient stability of AC systems considering the connected power-controlled grid-forming converters
下载PDF
导出
摘要 为研究功率控制型构网变流器接入交流系统后的暂态稳定性演化趋势,基于IEEE 39节点交流测试系统,将发电机分别等容量替换为功率控制型构网变流器与跟网型变流器,并改变其在交流系统中接入数量、并网位置进行电磁暂态仿真,结果表明:功率控制型构网变流器对接入区域的暂态稳定性提升能力更优,尤其当所替换发电机相邻时,提升效果显著;随着功率控制型构网变流器接入系统比例增加,系统暂态稳定性越强;功率控制型构网变流器内部等效惯性系数越大,系统同步稳定性越弱,其内部阻尼系数越大,系统同步稳定性越强。 To investigate the evolution trend of transient stability of power-controlled grid-forming(GFM)converters connected to AC systems,generators are replaced with power-controlled grid-forming(GFM)converters and gridfollowing(GFL)converters of equal capacity using the IEEE 39-bus AC test system.Additionally,the number of connections and integration positions in the AC system are varied for electromagnetic transient simulations.The results indicate that power-controlled grid-forming converters exhibit superior transient stability enhancement capabilities in the integration area,especially when the replaced generators are adjacent.As the proportion of such converters in the system increases,the system’s transient stability strengthens.Furthermore,higher equivalent inertia coefficients within power-controlled GFM converters lead to weaker synchronous stability of the system,whereas higher internal damping coefficients enhance synchronous stability.
作者 但扬清 黄莹 韩连山 王晨轩 武佳卉 刘青 徐政 DAN Yangqing;HUANG Ying;HAN Lianshan;WANG Chenxuan;WU Jiahui;LIU Qing;XU Zheng(Economic Research Institute of State Grid Zhejiang Electric Power Company,Hangzhou 310008,China;College of Electrical Engineering,Zhejiang University,Hangzhou 310027,China;NR Electric Co.,Ltd.,Nanjing 211102,China)
出处 《浙江电力》 2024年第6期1-12,共12页 Zhejiang Electric Power
基金 国网浙江省电力有限公司科技项目(5211JY21N001)。
关键词 功率控制型构网变流器 跟网型变流器 暂态稳定 等效惯性系数 阻尼系数 power-controlled GFM converter GFL converter transient stability equivalent inertia coefficient damping coefficient
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部