Arc Grounding Fault Identification Using Integrated Characteristics in the Power Grid

下载PDF
导出
摘要 Arc grounding faults occur frequently in the power grid with small resistance grounding neutral points.The existing arc fault identification technology only uses the fault line signal characteristics to set the identification index,which leads to detection failure when the arc zero-off characteristic is short.To solve this problem,this paper presents an arc fault identification method by utilizing integrated signal characteristics of both the fault line and sound lines.Firstly,the waveform characteristics of the fault line and sound lines under an arc grounding fault are studied.After that,the convex hull,gradient product,and correlation coefficient index are used as the basic characteristic parameters to establish fault identification criteria.Then,the logistic regression algorithm is employed to deal with the reference samples,establish the machine discrimination model,and realize the discrimination of fault types.Finally,simulation test results and experimental results verify the accuracy of the proposed method.The comparison analysis shows that the proposed method has higher recognition accuracy,especially when the arc dissipation power is smaller than 2×10^(3) W,the zero-off period is not obvious.In conclusion,the proposed method expands the arc fault identification theory.
出处 《Energy Engineering》 EI 2024年第7期1883-1901,共19页 能源工程(英文)
基金 This work was supported in part by the Natural Science Foundation of Henan Province,and the specific grant number is 232300420301。