摘要
通过对某海上风电场35 kV集电线跳闸进行检查分析,确定集电线断路器跳闸的原因是集电线上连接的3#风机海缆终端头被击穿,造成单相接地故障。3#风机海缆终端头更换后送电时3#风机断路器跳闸,检查发现3#风机断路器TA二次接线端子松动,引起自产零序电流过流,造成零序保护误动,使断路器跳闸。
This article analyzes and inspects the tripping of the 35 kV collector line of a certain offshore wind farm,and determines that the cause of the circuit breaker tripping of the collector line is the breakdown of the submarine cable terminal of the 3#wind turbine connected to the collector line,causing a single-phase grounding fault.After replacing the submarine cable terminal of the 3#wind turbine,the circuit breaker of the 3#wind turbine tripped during power transmission.Upon inspection,it was found that the CT secondary wiring terminal of the 3#wind turbine circuit breaker was loose,causing the self-produced zero sequence current to overcurrent,resulting in misoperation of the zero sequence protection and causing the circuit breaker to trip.
作者
张金博
ZHANG Jinbo(Zhejiang Zheneng Jiaxing offshore wind power Co.,Ltd,Zhejiang Jiaxing 314050,China)
出处
《农村电气化》
2024年第6期87-89,共3页
Rural Electrification