针对一起变电站中性点接地方式改造过程中零序跳闸事件,提出10 kV电缆线路的典型拓扑结构。结合实际工作,阐述当前试点应用中的经消弧线圈并联小电阻接地方式,并给出零序保护定值推荐值。结合案例,全面分析接地变跳闸逻辑错误、电缆线路FA自愈失败等故障原因,并提出改进措施。
The typical topological structure of 10 kV cable line is summarized and proposed according to the zero sequence trip event during the transformation of neutral grounding mode of substation.Combined with the practical work,the parallel small resistance grounding mode with arc suppression coil in the current pilot application is introduced in detail,and the recommended value of zero sequence protection is given.Combined with the case,the fault treatment process is explained in depth,the fault causes such as ground change tripping logic error and FA self-healing failure of cable lines are comprehensively analyzed,and the improvement measures are proposed,which lays a practical foundation for the key work of rapid isolation of grounding fault of urban distribution network.
作者
张启亮
刘倩影
ZHANG Qiliang;LIU Qianying(State Grid Jining Power Supply Company,Jining 272000,China)
出处
《黑龙江电力》
CAS
2024年第3期196-201,共6页
Heilongjiang Electric Power
关键词
消弧线圈
低电阻
单相接地故障
arc suppression coil
low resistance
single phase ground trip
rapid fault isolation