摘要
本文旨在对改造后的空调室内机进行研究。改造后的1.5P新风除湿空调开启除湿模式,其除湿量为1.58L/h,实测1.5P分体式空调的除湿量为1.44L/h,相比之下新风除湿空调的除湿量提高了10%左右。以厂房办公室为测试对象,对比新风除湿空调和某品牌分体式空调在使用时室内温度、相对湿度和CO_(2)浓度的变化情况,测试结果表明,新风除湿空调在使用时可以引入室外新风,降低室内CO_(2)含量,与分体式空调相比舒适度更高。因此新风除湿空调适用于低温高湿,空气质量要求较高的房间中。
This paper aims to research on the transformation of indoor air conditioning units.The dehumidification capacity of 1.5P split air conditioner is 1.44L/h,while the dehumidification capacity of 1.5P fresh air dehumidification air conditioning is 1.58L/h when the dehumidification mode is turned on after the transformation,which is about 10%higher.Taking the plant office as the test object,this study compared the changes in indoor temperature,relative humidity,and CO_(2) concentration between fresh air dehumidification air conditioning and a certain brand of split-type air conditioning when using.The test results show that the fresh air dehumidification air conditioning can introduce outdoor fresh air to downgrade the indoor CO_(2) concentration,and the fresh air dehumidification air conditioning is more comfortable compared to split-type air conditioning.Therefore,the fresh air dehumidification air conditioning is suitable for the room with low temperature,high relative humidity and high air quality requirements.
作者
么莉丹
吴旻
YAO Lidan;WU Min(Wuyi University)
出处
《广东建材》
2024年第7期110-113,共4页
Guangdong Building Materials
关键词
新风除湿空调
除湿量
CO_(2)浓度
舒适度
Fresh air dehumidification air conditioning
Dehumidification capacity
CO_(2)concentration
Comfort