期刊文献+

电流互感器内置防开路模块故障分析与选型策略

Fault Analysis and Selection Strategy of Built-In Anti-Open Circuit Module of Current Transformer
下载PDF
导出
摘要 针对近年某地区一起一二次融合ZW32-12型柱上断路器的故障进行了技术分析与试验验证,通过录波数据查找事故原因,发现故障发生的根本原因是电流互感器内置防开路模块启动电压的设计余量小。阐述了防开路模块的作用和原理,通过理论计算和试验验证给出了防开路模块启动电压的设计依据。经更换合理启动电压的防开路模块及时避免同类故障的再次发生,提升柱上断路器的入网质量,保障了配网的安全稳定运行。 In recent years,a primary and secondary fusion ZW32-12 type pole circuit breaker failure was technically analyzed and verified by experiments.The accident cause was searched through the recorded wave data,it was found that the root cause of the fault was the small design margin of the starting voltage of the built-in anti-open circuit module of current transformer.In this paper,the function and principle of anti-open circuit module are briefly described,and the design basis of starting voltage of anti-open circuit module is given through theoretical calculation and experimental verification.Replacing the anti-open circuit module with reasonable starting voltage to avoid the recurrence of similar faults in time,and improve the network access quality of the circuit breaker on the column,thus ensuring the safe and stable operation of the distribution network.
作者 夏鑫 吴秋亮 周世钢 XIA Xin;WU Qiu-liang;ZHOU Shi-gang(Jiangsu NARI Power Electric Co.,Ltd,Nanjing 211100,China)
出处 《电工电气》 2024年第7期53-56,共4页 Electrotechnics Electric
基金 国网电力科学研究院科技项目(524638240004)。
关键词 一二次融合柱上断路器 电流互感器 防开路模块 伏安特性 选型策略 primary and secondary fusion column circuit breaker current transformer anti-open circuit module volt-ampere characteristic selection strategy
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部