摘要
本文作者简述了某发电厂#3主变压器绝缘油含气量超标的情况,通过对#3主变压器本体和储油柜密封性试验检查,发现储油柜连通阀阀板关闭不严是导致含气量超标主要原因并进行了更换处理,通过抽真空热油循环滤油脱气处理了含气量超标的缺陷,并提出预防措施。
The situation of excessive gas content of insulation oil of#3 main transformer in the power plant is briefly described.After conducting sealing tests on the#3 main transformer body and conservator,it is found that the loose closure of the valve plate of the conservator connecting valve is the main cause of the gas content exceeding the standard,and replacement measures are taken.The defect of the gas content exceeding the standard is treated by vacuum hot oil circulation,oil filtration,and degassing,and preventive measures are proposed.
作者
年泓昌
NIAN Hongchang(China Resources Power Xinzhou Company,Xinzhou 034000,China)
出处
《变压器》
2024年第8期73-75,共3页
Transformer
关键词
变压器
含气量
储油柜
连通阀
Transformer
Gas content
Conservator
Connecting valve