摘要
介绍了一起换流站500kV交流滤波器断路器分闸时重击穿故障,通过解体检查、化学分析、电场仿真等手段进行原因分析,可知断口内固体微粒引起电场畸变,造成重击穿。
In this paper,the heavy breakdown fault of a 500 kV AC filter breaker in a converter station is introduced.The fault was analyzed by means of disassembly inspection,chemical analysis and electric field simulation.The solid particles in the fracture caused electric field distortion and caused rebreakdown.
作者
沈润鹏
周凯峰
王明
王俊娜
SHEN Runpeng;ZHOU Kaifeng;WANG Ming;WANG Junna(State Grid Shanghai Ultra High Voltage Company,Shanghai 200063,China)
出处
《电工技术》
2024年第S01期235-236,共2页
Electric Engineering
关键词
500KV断路器
固体微粒
电场畸变
重击穿
500 kV circuit breaker
solid particles
electric field distortion