期刊文献+

基于超声波的10kV电缆中间接头故障类型识别方法

Fault Type Identification Method of 10kV Cable Intermediate Joint Based on Ultrasonic
下载PDF
导出
摘要 电缆中间接头是连接两端电缆的关键附件,其绝缘状态及故障类型的准确识别是运维检修的关键工作,因此,设计制作了典型的中间接头故障样本,基于超声波局部放电测试方法,采用DWT法对测试数据进行降噪处理,并结合LeNet-5卷积神经网络架构提出了10kV电缆中间接头故障类型识别方法。结果表明,所提方法可以有效识别不同类型的电缆中间接头故障类型,识别准确率可达94%,为电缆的运维检修提供了一种新的方法。 Cable intermediate joint is a crucial accessory that connects two cable ends.The accurate identification of its insulation status and fault types is a key task for operation and maintenance.Therefore,typical fault samples of intermediate joint were designed and made,and a 10kV cable intermediate joint fault type identification method based on the ultrasonic partial discharge testing method and DWT method for denoising the test data,combined with the LeNet-5 convolutional neural network architecture,was proposed.The results show that the proposed method can effectively identify different types of cable intermediate joint faults with an accuracy rate of up to 94%,providing a new method for the operation and maintenance of cables.
作者 杜华 张乐乐 杨为波 赵步宽 张祥宇 DU Hua;ZHANG Le-le;YANG Wei-bo;ZHAO Bu-kuan;ZHANG Xiang-yu(Shijiazhuang Power Supply Section of China Railway Beijing Bureau Group Co.Ltd.,Shijiazhuang 050000,China;Southwest Jiaotong University,Chengdu 611756,China)
出处 《电气开关》 2024年第4期32-34,共3页 Electric Switchgear
关键词 电缆 中间接头 局部放电 超声波 故障识别 cable intermediate joint partial discharge ultrasonic fault identification
  • 相关文献

参考文献4

二级参考文献24

共引文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部