在“沙戈荒”地区风电经电网换相高压直流输电(line-commutated-converter based high voltage direct current,LCC-HVDC)外送系统中,采用基于匹配控制的构网型直驱风机(matching control permanent magnet synchronous generator,MC-PMSG)可以提升送端电网的稳定性。然而,当MC-PMSG位于LCC-HVDC整流站近区时,系统的次同步振荡(sub-synchronous oscillation,SSO)特性尚未明确。针对上述问题,该文采用模块化建模法建立MC-PMSG经LCC-HVDC送出系统的小信号模型,通过特征值法研究MC-PMSG与LCC-HVDC对系统各SSO模态的参与情况与系统运行方式变化对次同步振荡阻尼特性的影响,通过阻尼重构法分析LCC-HVDC并网对系统振荡风险的影响机理。研究结果表明,系统存在匹配控制型风机主导、LCC-HVDC参与的SSO模态,MC-PMSG与LCC-HVDC间的次同步交互作用为SSO提供负阻尼;当混合型风电场中的MC-PMSG占比增大、MC-PMSG风电场容量增大或短路比减小、LCC-HVDC定电流控制器的比例系数增大、风机网侧换流控制器外环积分系数减小、直流电容增大时,SSO阻尼增大。通过PSCAD/EMTDC电磁暂态仿真证明理论分析结果的有效性。
The matching-control-based grid-forming permanent magnet synchronous generator(MC-PMSG)can improve the voltage stability of the sending-end power grid in the line-commutated-converter based high voltage direct current(LCC-HVDC)transmission system of wind power in desert and Gobi regions.However,when the MC-PMSG is situated in the vicinity of LCC-HVDC rectifier station,the SSO features are indeterminacy.Aiming at above-mentioned problems,a small-signal model of MC-PMSG through the LCC-HVDC transmission system is erected by using the modularization modeling technique.The eigenvalues are used to study the participation of the MC-PMSG and LCC-HVDC in each SSO mode of the system and the consequence of system parameter changes on SSO damping characteristics.The mechanism of LCC-HVDC grid connection consequence on the SSO damping is analyzed by the damping reconstruction method.The results indicate that an SSO mode in the system is dominated by MC-PMSG,synchronously participated by LCC-HVDC.LCC-HVDC provides negative damping for this SSO mode.When the proportion of the MC-PMSG in the hybrid wind farm increases,the capacity of MC-PMSG increases or the short circuit ratio decreases,the proportional coefficient of the LCC-HVDC constant current controller increases,the integral coefficient of the wind turbine GSC outer loop decreases,or the DC capacitance increases,and the SSO damping increases.The PSCAD/EMTDC electromagnetic transient simulation is used to validate the validity of the theoretical analysis.
作者
高本锋
董涵枭
孙大卫
吴林林
王潇
邓晓洋
GAO Benfeng;DONG Hanxiao;SUN Dawei;WU Linlin;WANG Xiao;DENG Xiaoyang(Hebei Key Laboratory of Distributed Energy Storage and Micro-grid(North China Electric Power University),Baoding 071003,Hebei Province,China;State Grid Wind-photovoltaic-energy Storage Hybrid Power Generation Technology Laboratory(North China Electric Power Research Institute Co.,Ltd.),Xicheng District,Beijing 100045,China)
出处
《中国电机工程学报》
EI
CSCD
北大核心
2024年第23期9296-9309,I0016,共15页
PROCEEDINGS OF THE CHINESE SOCIETY FOR ELECTRICAL ENGINEERING
基金
国家重点研发计划项目(2021YFB2400800)。
关键词
电网换相高压直流输电
构网型直驱风机
匹配控制
次同步振荡
特征值分析
阻尼重构
line-commutated-converter based high voltage direct current(LCC-HVDC)
grid-forming direct drive wind farm
matching control
sub-synchronous oscillation(SSO)
eigenvalue analysis
damping reconstruction