期刊文献+

谐波对真空开关分断性能的影响

Influence upon the Breaking Capacity of Vaccum Circuit Breaker by Harmonic Current
下载PDF
导出
摘要 用数值计算方法具体计算了含谐波电流的最大值 ,发现即使在谐波电流总畸变率满足国标要求的情况下电流最大值还有可能远比基波最大值大。这虽不会影响真空断路器的分断能力及电寿命 ,但对真空负荷开关影响很大 ,有可能使真空负荷开关分断失败 ,使其电寿命大大缩短。因此 ,用熔断器 真空负荷开关来代替断路器的使用场合 。 The peak value of the current with harmonic component was computed simulately in this paper. The result shows that the peak value increases quite a lot even the total harmonic distortion of the complex current is in the level stipulated by the national standard. The increased current peak level will not impair the breaking capacity and the electric endurance of the vacuum circuit breaker while it will decrease those of the vacuum load switch, which should be paid more attention when the fuse vacuum circuit breaker combination is used to avoid the failed breaking and the shorten electric endurance.
出处 《低压电器》 2002年第5期10-12,19,共4页 Low Voltage Apparatus
基金 上海市教委青年基金资助项目
关键词 谐波 真空开关 分断性能 电寿命 真空断路器 harmonic vacuum circuit breaker breaking capacity electric edurance
  • 相关文献

参考文献2

  • 1于季梅.真空开关理论及其应用[M].西安:西安交通大学出版社,1986..
  • 2王兆安.谐波抑制入无功功率补偿[M].北京:机械工业出版社,2001..

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...