摘要 对一起 110kV变电站双绕组主变压器油温升高的故障进行深入分析。通过变压器油中溶解气体色谱分析 ,采用三比值法、四比值法和估算过热温度等化学分析手段初步推断主变压器可能的故障原因及严重程度 ,再结合电气试验较准确判断出主变压器的过热性故障性质和范围。尝试用故障排除法、敲击振动法、电容放电消除法等故障排除方法 ,在较短的时间内消除故障。 The fault of abnormal high oil temperature of the two windings main transformer in a 110 kV substation was discussed in detail. Chromatographic analysis for dissolved gas in transformer oil was used. Possible reasons and impacts on the main transformer were deduced preliminarily by three ratios method, four ratios method. Fault removing method, beating method, and capacitance electric discharge method were tried. The fault was eliminated in short time.
作者 黄炳洪
机构地区 龙岩电业局
出处 《电力情报》 2001年第4期46-49,共4页 Information on Electric Power
关键词 龙岩城关变电站 主变压器 油温升高 诊断 电力变压器 故障处理 main transformer abnormal high oil temperature analysis treatment
  • 相关文献

参考文献2

  • 1GB 7252/87,变压器油中溶解气体分析和判断导则[S].北京:中国标准出版社,1993
  • 2山西省电力工业局.电厂化学设备运行[M].北京:中国电力出版社,1997..