期刊文献+

开洞T形圆钢管相贯节点极限承载力研究 被引量:1

RESEARCH ON THE ULTIMATE BEARING CAPACITY OF CHS T-TYPE JOINTS WITH OPENING
原文传递
导出
摘要 为分析开洞T形圆钢管相贯节点极限承载力,确定开洞率对节点极限承载力的影响规律,并给出T形圆钢管相贯节点的开洞设计建议。首先对支管轴心受力T形圆钢管相贯节点的受力机理进行了阐述,建立了参数化节点有限元计算模型,参数包括:支主管管径比、支主管管壁厚度比、开洞率和支管受力状态,并对160个支管轴心受力节点模型进行了非线性有限元分析。结果表明:开洞对支管轴心受拉节点的影响大于支管轴心受压节点;其他条件不变时,支管壁厚越大,极限承载力也越大;满足一定条件时,支管轴心受压T形圆钢管相贯节点开洞率可取到0. 5,而支管轴心受拉节点开洞率只可取到0. 25。 The paper analyzed the ultimate bearing capacity of circular hollow section( CHS) steel T-type joints under axial force applied to branch member,revealed the regularity of the effect of the opening on the ultimate bearing capacity of CHS steel T-type joints,and advised the design proposals for opening rate of CHS steel T-type joints.Firstly,the forced mechanism of circular hollow section( CHS) steel T-type joints under axial force applied to branch member was expounded. Then,the parametric finite element models were established for the T-type joints. The calculation parameters include diameter ratio of branch member to chord member,wall thickness ratio of branch to chord,opening rate and force state of branch member. Based on the nonlinear finite element method,160 T-type joint models were analyzed. The effect of opening ratio on the T-type joint with tensile branch was greater than that of the T-type joint with compressive branch;when other conditions remained the same,the larger the branch wall thickness was,the greater the ultimate bearing capacity was. Under a certain condition,the opening ratio of the T-type joint with compressive branch could reach to 0. 5,while the opening ratio of the T-type joint with tensile branch should less than or equal to 0. 25.
作者 赵俊钊 陈颖 ZHAO Junzhao;CHEN Ying(Shanghai Construction No.4 ( Group) Co. Ltd,Shanghai 201103,China)
出处 《工业建筑》 CSCD 北大核心 2019年第1期163-169,共7页 Industrial Construction
基金 上海建工集团股份有限公司重点科研项目(17JCSF-02)
关键词 T形相贯节点 开洞率 轴心受力 极限承载力 T-type joint opening ratio axial force ultimate bearing capacity
  • 相关文献

参考文献5

二级参考文献35

  • 1戴雅萍,赵宏康.苏州国际博览中心钢结构楼面设计[J].钢结构,2005,20(6):36-39. 被引量:2
  • 2武振宇,张耀春.直接焊接钢管节点静力工作性能的研究现状[J].哈尔滨建筑大学学报,1996,29(6):102-109. 被引量:34
  • 3鲁琛.空间直接焊接圆钢管节点足尺试验研究,硕士学位论文[M].同济大学,2000..
  • 4同济大学钢结构研究室.成都双流机场扩建工程航站楼钢结构屋盖结构试验研究与分析--相贯节点试验报告[M].,2000..
  • 5张志良.焊接方管节点极限承载力的试验研究和非线性有限元分析,硕士学位论文[M].同济大学,1988..
  • 6刘鹏.方圆汇交平面钢管节点的刚度研究,硕士学位论文[M].同济大学,2001..
  • 7Packer J A 等 曹俊杰(译).空心管结构连接设计指南[M].科学出版社,1997..
  • 8GB50011-2010,建筑抗震设计规范[S].
  • 9JGJ7-2010空间网格结构技术规程[S].
  • 10JGJ3-2010,高层建筑混凝土结构技术规程[S].

共引文献151

同被引文献2

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部