摘要
介绍了鹤岗发电有限责任公司300MW机组锅炉回转式空气预热器的漏风情况,分析了造成空气预热器漏风的各种因素,指出了由于转子不垂直、扇形板不水平、各部密封间隙设计不合理是造成回转式空气预热器漏风的主要原因。通过理论计算提出了解决方案,重新调整各部密封间隙值,使空气预热器的漏风问题有了很大的改善,提高了锅炉效率,获得很大的经济效益。
All the causes for the air leakage from the rotary air preheater are analysed ,and non-vertical rotor,non-flat quadrant pa nel and non-rational design of sealing gap are c onsidered primary causes, and the sealing g ap newly-established through theoretical calcula tion significantly reduced the air leakage thereby improving the boiler efficiency.
出处
《黑龙江电力》
CAS
2002年第6期468-469,共2页
Heilongjiang Electric Power