介绍了一起由10kV线路故障引起智能变电站跳闸的事件,分析了保护装置和电子互感器的动作行为,论证了该事件中保护动作正确,电子互感器存在缺陷。
This paper introduces an accident about 110 kV smart substation trip caused by 10 kV transmission line,then analyzes the actions of relay protection and the electronic transformers.The actions of relay protection are proved correct and the electronic transformers are found to be defective.
出处
《湖北电力》
2014年第12期29-33,共5页
Hubei Electric Power
关键词
智能变电站
跳闸
继电保护
电子互感器
smart substation
trip
relay protection
electronic transformer