期刊文献+

基于智能切负荷方式的武汉220kV变电站备自投逻辑改进与分析 被引量:1

Analysis on Logic of Automatic Bus Transfer for Wuhan 220kV Substations and Its Improvement Based on Intelligent Load Shedding
下载PDF
导出
摘要 综合考虑武汉地区部分220kV变电站所供10kV用户负荷的重要性,针对原备自投装置存在主变故障时10kV负荷无法转带,且在高峰负荷时因负荷电流闭锁备自投导致损失负荷严重等问题,对备自投逻辑进行了分析改进,提出了新的动作逻辑策略,同时实现了智能切除部分负荷,有效避免了主变过载。 In view of the importance of the 10 kV customer load supplied by the 220 kV substations in Wuhan,this article analyses and improves the logic of the automatic bus transfer,which solved the problems such as the 10 kV load transfer in main transformer fault and load losing caused that the au-tomatic bus transfer is blocked by the load current in the peak load.The new action logic strategy is proposed.At the same time,the intelligent partial load shedding is achieved,which effectively avoids the main transformer overload.
作者 张囡 李豪
出处 《湖北电力》 2015年第6期24-26,39,共4页 Hubei Electric Power
关键词 备自投 智能切除负荷 主变过载 automatic bus transfer intelligent load shedding main transformer overload
  • 相关文献

参考文献3

二级参考文献5

  • 1冯匡一.袁季修.宋继成.等.GB/T14285-2006继电保护和安全自动装置技术规程[S].北京:中华人民共和国国家标准化委员会.2006.
  • 2RCS-9651C_090381备用电源自投装置说明书[z].南瑞继保,2009.
  • 3崔家佩,孟庆炎,陈永芳,等.电力系统继电保护与安全自动装置整定计算[M].中国电力出版社,1999.
  • 4变电站备用电源自动投入装置技术导则[S].湖北省电力公司,2004.
  • 5刘继文.单母线三分段接线的备自投实现方式[J].电工技术,2007(11):3-4. 被引量:2

共引文献15

同被引文献14

引证文献1

二级引证文献2