摘要
以白山市CAST工艺污水处理厂工程为实例,归纳总结自动控制系统设计方案、系统组成及其功能,阐述控制策略,并利用污水厂运行结果对控制系统性能及控制策略进行评价。运行结果表明,采用自动控制系统后,污水处理厂运行稳定性提高,出水达标率可达80%,且吨水耗电量也较低,约为0.30 kW·h/m3。
The CAST reactor in wastewater treatment plant in Baishan City was take as the example to summarize the automatic control system design,system components,and their functions,elaborate control strategies. Evaluation on the control performance and strategy of the system were conducted based on running results. The results showed that the automatic control system improve the stability of the wastewater treatment plant operation. 80% of the effluent meets the emission standard requirements,and power consumption gets as low as 0. 30 kW·h /m2.
出处
《环境工程》
CAS
CSCD
北大核心
2014年第11期1-4,10,共5页
Environmental Engineering
基金
国家自然科学基金(51308253)
吉林省科技发展计划资助项目(20130522076JH)
关键词
污水处理厂
自动控制
PLC控制
wastewater treatment plant
automatic control
PLC control