保护装置开关操作回路的设计优化 被引量:4

Design optimization of switch operating circuits in protective equipment
下载PDF
导出
摘要 针对目前的保护产品在工程现场经常发生开关机构因某种原因而失灵拒动,造成分合闸回路长期保持而烧毁分合闸线圈的问题,分析了典型操作回路,选择小型大容量电磁中间继电器作为操作执行的重动中间,将微机装置出口接点设置为有限延时,通过切断低功耗的分合闸重动回路间接解除操作回路的保持,有效解决了命令保持与开关机构失灵的矛盾。实践表明改造后的方案既有效保证了正常情况下可靠分合闸,又在异常时保证操作回路设备的完好,并能及时上报开关失灵远方信号。 When the switching mechanism fails action,the current keeps in the trip or close cir cuits of protective equipment for a long period,which may damage the trip of close winding.Based on the analysis of typical operating circuits,a solution is proposed to treat between command holding and mechanism failure.A miniature interposing relay is used and the output contact of protective equipment is set for a limited time delay for releasing the command holding of trip/close circuits.The practice shows that the improved circuits ensure the reliable trip or close of breaker under normal conditions and prevents the damage of operating circuits under abnormal conditions.In addi-tion,it can send upward the remote signal of breaker failure in time.
机构地区 唐山供电设计院
出处 《电力自动化设备》 EI CSCD 北大核心 2003年第3期85-87,共3页 Electric Power Automation Equipment
关键词 保护装置 开关操作回路 设计优化 电力系统 微机保护 继电保护 protective equipment switching mechanism failure design optimization
  • 相关文献

参考文献2

  • 1西北电力设计院.电力工程电气设计手册(电气二次部分)[M].北京:中国电力出版社,1991.Northwest power design institute. Design manual of electric power engineering(second part of electricity)[M].Beijing: China Electric Power Press, 1991.
  • 2工厂常用电气设备手册编写组.工厂常用电气设备手册(下册)[M].北京:水利电力出版社,1993.The editor of manual of electrical equipment for factory. Manual of electrical equipment for factory(volume Ⅱ)[M].Beijing:Hydraulic and Electric Power Press, 1993.

同被引文献9

引证文献4

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部