期刊文献+

220kV变电站主变有载分接开关重瓦斯继电器跳闸故障原因分析 被引量:4

Fault Analysis on On-load Tap Switch Heavy Gas Relay Tripping for 220 kV Main Transformer
下载PDF
导出
摘要 针对近期一起典型东北电力系统发生的变电站主变有载分接开关重瓦斯跳闸故障进行分析,提出呼吸器受潮冷冻后回温重新呼吸及变压器内油温上升造成油流涌动是引起该类故障的原因,并进行了相应的模拟试验。 According to heavy gas relay tripping fault of on- load tap switch for main transformer of northeast electric system,its fault causes are analyzed. This paper proposes that breather can reuse after frozen when it becomes damp,the cause of failure is that oil surging caused by oil temperature rise in the transformer,simulation test is carried out.
出处 《东北电力技术》 2015年第8期17-20,共4页 Northeast Electric Power Technology
关键词 有载分接开关 重瓦斯继电器 多次跳闸 呼吸器受潮 On-load tap switch Heavy gas relay Multiple tripping Breather damp
  • 相关文献

参考文献3

二级参考文献4

  • 1DL/T572-1995[S].电力变压器运行规程.
  • 2中国电力出版社.国家电网公司十八项电网重大反事故措施[M].北京:中国电力出版社,2005.
  • 3郑岩.电力变压器的保护动作分析及处理[EB/OL].安全文化网,http://www.anquan.com.cn/Tech/ShowArticle.asp?ArticleID=25967.
  • 4徐康健.变压器瓦斯保护动作案例的分析[J].变压器,2009,46(4):75-76. 被引量:6