期刊文献+

多时变扰动下的PID控制性能评估 被引量:1

Performance assessment of PID control with multiple time-varying disturbance
原文传递
导出
摘要 时变扰动是影响控制系统性能的主要因素之一。针对存在多个时变扰动的情况,提出了一种基于多模型加权的PID最小可达方差控制性能评估方法。首先,根据每个扰动的特性设计子PID最小可达方差控制器;然后,基于扰动作用时间构造权重以设计多模型加权控制器,再以此控制器作用下系统输出所能达到的最小方差作为基准评估PID控制系统的性能。最后,通过仿真实例验证所提方法的有效性。 Time-varying disturbance is one of the main factors affecting the performance of the control system.For the case of multiple time-varying disturbances,a PID achievable minimum variance performance assessment method based on multi-model weighted is proposed.First,a PID achievable minimum variance controller is designed based on the characteristics of each disturbance.Then,multiple controllers are weighted based on the disturbance time and the achievable minimum variance of the system output under the weighted controller is used as a benchmark for performance assessment.Finally,the effectiveness of the proposed method is verified by simulation examples.
作者 徐锐 王志国 赵顺毅 刘飞 XU Rui;WANG Zhiguo;ZHAO Shunyi;LIU Fei(Key Laboratory of Advanced Process Control for Light Industry(Ministry of Education),Institute of Automation,Jiangnan University,Wuxi 214122,Jiangsu,China)
出处 《计算机与应用化学》 CAS 北大核心 2019年第1期9-16,共8页 Computers and Applied Chemistry
基金 国家自然科学基金项目(61773183)
关键词 性能评估 时变扰动 PID最小可达方差 多模型加权 performance assessment time-varying disturbance PID achievable minimum variance multiple-model weighted
  • 相关文献

参考文献1

二级参考文献16

  • 1王昕 ,李少远 ,岳恒 .Multivariable Adaptive Decoupling Controller Using Hierarchical Multiple Models[J].自动化学报,2005,31(2):223-230. 被引量:7
  • 2Astrom K J. Introduction to Stochastic Control Theory. New York: Academic, 1970.
  • 3Harris T. Assessment of control loop performance. Canadian Journal of Chemical Engineering, 1989, 67(5): 856-861.
  • 4Stanfelj N, Marlin T E, MacGregor J F. Monitoring and diagnosing process control performance: the single-loop case. Industrial and Engineering Chemistry Research, 1993, 32(2): 301-314.
  • 5Tyler M, Morari M. Performance assessment for unstable and nonminimum-phase systems. In: Proceedings of the 1996 IFAC Workshop on On-Line Fault Detection and Supervision in the Chemical Process Industries. Tyne, UK: IFAC, 1996. 187-192.
  • 6Olaleye F, Huang B, Tamayo E. Performance assessment of control loops with time-variant disturbance dynamics. Journal of Process Control, 2004, 14(8): 867-877.
  • 7Zhou M F, Xie L, Pan H T,Wang S Q. Performance assessment of PID controller with time-variant disturbance dynamics. In: Proceedings of the 2011 International Symposium on Advanced Control of Industrial Processes. Hangzhou, China: IEEE, 2011. 650-655.
  • 8Huang B. Minimum variance control and performance assessment of time variant processes. Journal of Process Control, 2002, 12(6): 707-719.
  • 9Xu F W, Huang B. Performance monitoring of SISO control loops subject to LTV disturbance dynamics: an improved LTI benchmark. Journal of Process Control, 2006, 16(6): 567-579.
  • 10Huang B, Shah S L. Performance Assessment of Control Loops: Theory and application. New York: Springer, 1999.

共引文献10

同被引文献5

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部