期刊文献+

热回收型地源热泵系统经济性能分析及评价 被引量:1

Analysis and Evaluation of the Economic Performance of Ground Source Heat Pump System with Waste Heat Recover y
原文传递
导出
摘要 以夏热冬冷地区某酒店建筑的地源热泵系统为研究对象,运用动态费用年值法,从系统初投资、空调运行费用及制备生活热水费用三方面对不同方案的地源热泵系统进行经济性能评价。研究结果表明:与常规地源热泵相比,热回收型地源热泵工程的全寿命周期的综合效益优势明显,其中,50%的热回收型地源热泵系统动态费用年值最小,最为经济,节能效果最明显。 Economic performance of initial investment, operational cost and supplying cost of domestic hot water for different scenarios of ground source heat pump system(GSHPS), which is designed for a hotel located in the hot summer and warm winter area, have been analyzed using the dynamic annual cost method. The results show that the comprehensive benefit of GSHPS with waste heat recovery is distinct compared with conventional GSHPS. When the ratio of waste heat recovery is 50%, the dynamic annual cost of GSHPS is minimum and achieves the optimizing energy-saving effect.
出处 《建筑经济》 北大核心 2014年第8期133-136,共4页 Construction Economy
基金 江苏省产学研联合创新基金(BY2013066-09)
关键词 地源热泵 热回收 费用年值 全寿命周期 经济性分析 ground source heat pump heat recovery annual cost whole life cycle economic analysis
  • 相关文献

参考文献2

二级参考文献10

  • 1龚光彩,常世钧,马扬,曾巍,林鑫.蒸汽压缩式水冷制冷机的双冷凝器热回收技术[J].建筑热能通风空调,2005,24(1):6-12. 被引量:16
  • 2马最良,姚杨.民用建筑空调设计[M].北京:化学工业出版社,1986,173-190.
  • 3Yavuzturk C, Spitler J D. Comparative study of operating and control strategies for hybrid ground source heat pump systems using a short stimulation model [ J ]. ASHRAE Transactions, 2000,106 (2) : 192 - 209.
  • 4Kananaugh S P. A design method for hybrid ground - source heat pumps [ J ]. ASHRAE Transactions, 1998, 104(2) :691 -698.
  • 5吴存真,张诗针,孙志坚.热力过程火用分析基[M].杭州:浙江大学出版社,1991,220-231.
  • 6Michel A Bemier. Ground- coupled heat pump system simulation [ J ]. ASHREAE Transactions, 2001, AT01 - 8 - 3:605 - 616.
  • 7Remund C P. Borehole thermal resistance: Laboratory and field studies [ J ]. ASHRAE Transactions, 1999, 105 ( 1 ) :439 - 445.
  • 8Gu Y,ONeal D L. Modeling the effect of backfills on U -tube ground coil performance[ J ]. ASHRAE Transaction, 1998,104(2) :34 -41.
  • 9Ramamoorthy M,Jin H. Optimal sizing of hybrid ground - source heat pump systems that use a cooling pond as a supplemental heat rejecter -a system simulation approach [ J ]. ASHRAE Transactions, 2001,107 ( 1 ) :26 - 38.
  • 10Cane R L D, Eng P,Forgas D A. Modeling of Ground - Source Heat Pump Performance [ J ]. ASHRAE Transactions, 1991,97( 1 ) :909 - 925.