期刊文献+

三峡电站允许地电位升高试验研究(Ⅱ)——继电保护设备的工频耐压特性研究 被引量:18

TEST RESEARCH ON TOLERABLE GROUND POTENTIAL RISE OF THREE GORGES HYDROELECTRIC POWER STATION PART TWO: POWER FREQUENCY VOLTAGE WITHSTANDING CHARACTERISTICS OF PROTECTIVE RELAYS
下载PDF
导出
摘要 为了确定提高地网允许电位升高值是否可行,作者在研究了控制电缆的工频耐压特性之后在本文中又研究了继电保护设备的工频耐压特性对该值的影响,并进行了试验。结果表明,继电器绝缘的工频耐压特性是影响这一数值的关键因素。 To determine whether it is possible or not to increase the value of the tolerable ground potential rise, after the research of power frequency voltage withstanding characteristics of control cables in part one of this paper, the influence of power frequency voltage withstanding characteristics of protective relays on tolerable ground potential rise was studied and corresponding tests were carried out. The test results show that the power frequency voltage withstanding characteristics of the insulation of protective relays are the key factor influencing tolerable ground potential rise.
出处 《电网技术》 EI CSCD 北大核心 2003年第3期5-7,22,共4页 Power System Technology
基金 "九五"国家重点攻关项目(97-312-02-11)。
关键词 三峡电站 地电位升高 试验 继电保护设备 工频耐压特性 Three Gorges Power Plant GPR Relays Power Frequency Breakdown Characteristics
  • 相关文献

参考文献2

二级参考文献3

共引文献22

同被引文献284

引证文献18

二级引证文献330