摘要 热泵技术是当今建筑节能的重要技术之一,为了探究其实际的运行效果和节能减排量,对寒冷地区某办公建筑的污水源热泵系统进行研究,通过实地调研2016—2017年度冬季该系统运行性能的数据,分析了该污水源热泵系统在冬季的运行效果,并与冬季采用传统燃煤锅炉供暖方式进行比较,得到该系统供暖季的机组平均COP和系统平均EER分别为2.82和2.2,较传统燃煤锅炉供暖方式可以节省标煤260.8t,减少CO_2排放量为717.2t、SO_x排放量为1.04t、NO_x排放量为7.8t、粉尘量为5.2t。 Heat pump technology is one of the most important technologies for building energy conservation today. In order to explore its actual operation effect, energy saving and emission reduction, the sewage source heat pump system of an office building in the cold area is studied. Through field research on the system performance in the winter of 2016-2017, the operation effect of the sewage-source heat pump system in winter was analyzed, and compared with the traditional coal-fired boiler heating method in winter. The average COP and EER of the system in heating season are 2.82 and 2.2, respectively. It compares with the traditional coal-fired boiler heating mode, the system can save 260.8 t of standard coal, 717.2 t of CO2 emission, 1.04 t of SOx emission, 7.8 t of NOx emission and 5.2 t of dust emission.
作者 刘馨 隋红亮 梁传志 李宗翰 李画 吴玥 鲁倩男 Liu Xin;Sui Hongliang;Liang Chuanzhi;Li Zonghan;Li Hua;Wu Yue;Lu Qiannan(School of Municipal and Environmental Engineering,Shenyang Jianzhu University,Shenyang,Liaoning,110168;Center of Science and Technology and Industrialization,Beijing,100835)
出处 《建设科技》 2019年第2期26-31,共6页 Construction Science and Technology
基金 国家重点研发计划项目"公共机构高效节能关键技术应用示范效果评估"(2017YFB0604005)
关键词 污水源热泵 运行效果 节能减排量 sewage-source heat pump operation effect energy saving and emission reduction
  • 相关文献

参考文献2

二级参考文献15

  • 1刘海霞,杨洁,张旭,周翔.严寒地区复合地源热泵系统合理负荷分担率分析[J].制冷技术,2012,32(3):41-45. 被引量:4
  • 2谭乃秦.污水水源热泵空调技术利用[J].建设科技,2005(16):62-63. 被引量:1
  • 3刘洋,刘金祥,丁高.水源热泵机组变工况运行的数学模型研究[J].暖通空调,2007,37(3):21-24. 被引量:16
  • 4中国建筑科学研究院.GB50736-2012民用建筑供暖通风与空气调节设计规范[s].北京:中国建筑工业出版社,2012.
  • 5Shu Haiwen, Duanmu Lin, Zhang Chaohui, et al. Study on the decision-making of district cooling and heating sys- tems by means of value engineering [ J ]. Renewable Ener- gy, 2010, 35(9): 1929-1939.
  • 6Shu Haiwen, Duanmu Lin, Li Xiangli, et al. Energy-sav- ing judgment of electric-driven seawater source heat pump district heating system over boiler house district heating.system[J]. Energy & Buildings, 2010, 42(6) : 889-895.
  • 7Shu Haiwcn, Duanmu Lin, Li Xiangli, et al. Quasi-dy- namic energy-saving judgment of electric-driven seawater source heat pump district heating system over boiler house district heating system [ J ]. Energy & Buildings, 2010, 42 (12) : 2424-2430.
  • 8Li Zhen, Duanmu Lin, Shu Haiwen, et al. District cooling and heating with seawater as heat source and sink in Dalian, China[ J]. Renewable Energy, 2007, 32 ( 15 ) : 2603-2616.
  • 9Choi J M. Study on the LWT control schemes of a heat pump for hot water supply[ J]. Renewable Energy, 2013, 54 : 20-25.
  • 10Chua K J, Chou S K, Yang W M. Advances in heat pump systems:A review [ J]. Applied Energy, 2010,87 ( 12 ) : 36 1 1-3624.