期刊文献+

全封闭组合电器室SF_6气体泄漏分布规律与气体检测布置策略 被引量:18

The Distribution Law of SF_6 Gas Leakage and Gas Monitor Layout Strategy in Gas Insulated Substation
下载PDF
导出
摘要 全封闭组合电器(GIS)在运行过程中不免故障,会出现SF_6气体泄漏的问题;这不仅会对设备维护人员的人身安全构成极大威胁,也会对环境造成难以估量的负面影响。目前,SF_6气体检测及回收装置布置策略缺乏理论指导。针对盆式绝缘子开裂而造成的SF_6气体泄漏事故,基于FLUENT软件,结合SF_6气体泄漏的两相流三维非定常态湍流流动特征,搭建三维传递现象模型;进行真型尺寸GIS站室泄漏SF_6气体分布规律仿真研究。分析了GIS设备因故障而发生气体泄漏时,SF_6气体扩散的过程及SF_6气云的分布规律;比较了不同位置、不同方向出现单点泄漏时SF_6气体的扩散分布情况。再结合GIS室实际空间布局,指出应在贴地安全警示带距离地面0.5 m处及GIS设备上方沿纵横方向均匀布置SF_6气体检测设备,形成立体的空间密集网状检测系统。 During the operation of gas insulated substation(GIS),there will be problems of SF6 gas leakage due to some failures,which will not only pose a great threat to the personal safety of equipment maintenance personnel,but also cause an incalculable negative impact on the environment.At present,the layout strategy of SF6 gas detection and recovery device lacks theoretical guidance.Taking the SF6 gas leakage accident caused by the cracking of basin insulator as an example,based on the FLUENT software,a three-dimensional transmission phenomenon was built,and simulated the distribution law of SF6 leaking gas in true-size GIS station.Combined with the threephase unsteady turbulent flow characteristics of two-phase flow of SF6 gas leakage,the process of SF6 gas diffusion and the distribution of SF6 gas cloud were analyzed when gas leakage occurs due to the faults of GIS equipment.And the distribution of SF6 gas diffusion at single point and leakage in different locations and directions was compared,which provided reference for the location of SF6 gas detection and also the arrangement of recovery device.In combination with the actual situation of the GIS station,the SF6 gas detection equipment should be installed at a grounding safety warning zone 0.5 m from the ground and evenly arranged in the vertical and horizontal directions above the GIS equipment to form a three-dimensional spatial dense mesh monitoring system.
作者 杨芮 赵建勇 石磊 王靖瑞 王健 李庆民 YANG Rui;ZHAO Jian-yong;SHI Lei;WANG Jing-rui;WANG Jian;LI Qing-min(SGCC Beijing Electric Power Research Institute,Beijing100075,China;School of Electrical and Electronic Engineering,North China Electric Power University,Beijing102206,China)
出处 《科学技术与工程》 北大核心 2019年第9期99-107,共9页 Science Technology and Engineering
基金 国家电网公司科技项目(SGBJDK00SPJS1800203)资助
关键词 GIS SF6气体泄漏 分布规律 气体检测布置策略 gas insulated substation SF6 gas leakage distribution law gas monitor layout strategy
  • 相关文献

参考文献10

二级参考文献67

共引文献77

同被引文献179

引证文献18

二级引证文献40

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部