期刊文献+

One-End Data Method for Fault Position Estimate of Two-Parallel Transmission Lines

One-End Data Method for Fault Position Estimate of Two-Parallel Transmission Lines
下载PDF
导出
摘要 An accurate numerical algorithm for three-line fault involving different phases from each of two-parallel lines is presented. It is based on one-terminal voltage and current data. The loop and nodel equations comparing faulted phase to non-faulted phase of two-parallel lines are introduced in the fault location estimation modal, in which the faulted impedance of remote end is not involved. The effect of load flow and fault resistance on the accuracy of fault location are effectively eliminated, therefore an accurate algorithm of locating fault is derived. The algorithm is demonstrated by digital computer simulations and the results show that errors in locating fault are less than 1%. An accurate numerical algorithm for three-line fault involving different phases from each of two-parallel lines is presented. It is based on one-terminal voltage and current data. The loop and nodel equations comparing faulted phase to non-faulted phase of two-parallel lines are introduced in the fault location estimation modal, in which the faulted impedance of remote end is not involved. The effect of load flow and fault resistance on the accuracy of fault location are effectively eliminated, therefore an accurate algorithm of locating fault is derived. The algorithm is demonstrated by digital computer simulations and the results show that errors in locating fault are less than 1%.
出处 《Journal of Beijing Institute of Technology》 EI CAS 2003年第1期105-108,共4页 北京理工大学学报(英文版)
基金 SponsoredbytheKeyScienceFoundationofTianjin(0 2 3 80 12 11)
关键词 power system two-parallel lines fault location estimation one-terminal data power system two-parallel lines fault location estimation one-terminal data
  • 相关文献

参考文献8

  • 1Djuric M B,Radojevic Z M,Terzija V V.Distance protection and fault location utilizing only phase current phasors[].IEEE PES Transaction on Power Delivery.1998
  • 2Kezunovic M,Perunicic B.Synchronized sampling improves fault location[].IEEE Computer Applications in Power.1995
  • 3Zamore I,Minambres J F,Mazon A J,et al.Fault location on two-terminal transmission lines based on voltages[].IEE Proceedings—Generation Transmission and Distribution.1996
  • 4Djuric M B,Radojevic Z M,Terzija V V.Time domain solution of fault distance estimation and arcing faults detection on overhead lines[].IEEE PES Transaction on Power Delivery.1999
  • 5Novosel D,Hart D G,Udren E,et al.Unsynchronized two-terminal fault location estimation[].IEEE Trans.1996
  • 6Kezunovic M,Perunicic B.Automated transmission line fault analysis using synchronized sampling at two end[].IEEE Trans.1996
  • 7Novosel D,Hart D G,Udren E,et al.Fault location using digital relay data[].IEEE Computer Applications in Power.1995
  • 8Zhang Qingchao,Zhang Yao,Song Wennan,et al.Fault location of two-parallel transmission line for nonearth fault using one-terminal data[].IEEE PES Transaction on Power Delivery.1999