期刊文献+

北京东环广场写字楼的多分区空调设计的探讨 被引量:2

Discussion of the multizone air conditioning system design of office towers in Beijing East Gate Plaza
下载PDF
导出
摘要 对比了中美办公楼空调系统选用上的差别及近年来的发展趋势 ,详细分析了风机盘管加新风空调系统与多分区集中空调系统两者的优点与缺点 ,认为对参数控制要求较高、每个风系统有 5个以上分区者 ,宜考虑选用变风量集中空调系统 ,而对每个风系统仅有 3个以下分区的开敞式建筑 ,如受造价制约 ,亦可选用多分区集中空调系统。 Compares the differences and trends in adopting air conditioning systems in China and the U.S., discusses in detail the advantages and disadvantages of the fan-coil unit plus fresh air system and the multizone system. Holds that the VAV central air conditioning system is preferable for stricter control requirements and each air system involving no less than five subzones while the multizone system is adoptable in an open building with the air system each involving up to three subzones and the VAV equipment is not acceptable for cost reason.
作者 汪善国
机构地区
出处 《暖通空调》 北大核心 2003年第1期32-35,共4页 Heating Ventilating & Air Conditioning
关键词 北京 东环广场 写字楼 空调设计 变风量 集中空调系统 风机盘管 新风空调系统 office building, fan-coil unit plus fresh air, variable air volume, multizone air conditioning system
  • 相关文献

参考文献9

二级参考文献9

共引文献40

同被引文献8

引证文献2

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部