12Cr1MoV钢高温过热器管爆裂分析 被引量:6

Burst Analysis on High Temperature Superheated Pipe of 12Cr1MoV Steel
下载PDF
导出
摘要 某电厂的12Cr1MoV钢高温段过热器管在使用2a(年)后发生爆裂。采用宏观和微观分析方法分析了爆裂的原因。结果表明:由于管壁穿孔引起锅炉的汽水循环不畅,高温过热器管局部超温运行,导致管材发生高温腐蚀及珠光体完全球化,引发多处横裂源,进一步导致两处发生同一径向的纵裂。 A high temperature superheated pipe of 12Cr1 MoV steel bursted after using for two years in a power plant.The burst reason was analyzed by means of macroscopic and microscopic examination.The results indicated that because of pipe wall perforation,the steam and water cycle was stumbled,the pipe had been operated under local overtemperature,which caused high temperature local corrosion and peralite spheroidization,many transverse fissures generated and the two longitudinal divisions was produced in the same radial direction.
作者 潘红涛
机构地区 酒泉钢铁公司
出处 《理化检验(物理分册)》 CAS 2014年第11期842-844,共3页 Physical Testing and Chemical Analysis(Part A:Physical Testing)
关键词 12CR1MOV钢 高温过热器管 爆裂 局部高温腐蚀 珠光体球化 12Cr1MoV steel high temperature superheated pipe burst high temperature local corrosion pearlite spheroidization