国家大剧院观众厅空调系统和气流组织方式的设计和分析 被引量:38

Design analysis of air conditioning and air distribution in the auditoria of the national theatre
下载PDF
导出
摘要 介绍了观众厅座椅下送风方案。通过对置换通风和空调系统下送风方式的分析和实测 ,总结出这种气流组织的设计计算方法。全年能耗分析显示 ,为达到高标准的卫生和舒适要求采用 30m3/h人均新风量的椅下送风空调方式 ,比 1 5m3/h人均新风量的混风变新风比空调系统制冷量增加 5 0 .9%。 Describes the under-seat air supply mode adopted in the project. Provides a procedure of design and calculation based on analyses and field measurement. An annual energy analysis shows that 50.9% more in the cooling capacity is required for the adopted under-seat air supply mode to meet higher standard of comfort and indoor air quality with 30 cubic metre per hour per person than that by using a mixing air conditioning system with a common fresh air supply of 15 cubic metre per hour per person.
出处 《暖通空调》 北大核心 2003年第3期1-8,共8页 Heating Ventilating & Air Conditioning
关键词 国家大剧院 观众厅 空调系统 气流组织 设计 置换通风 送风 national theatre, auditorium, under-seat air supply, displacement ventilation, design calculation, energy analysis
  • 相关文献

参考文献6

  • 1周鹏,李强民.置换通风与冷却顶板[J].暖通空调,1998,28(5):1-5. 被引量:45
  • 2李强民 孟广田 张富成 等.座椅送风系统的特性研究[A]..全国暖通空调制冷1998年学术年会文集[C].北京:中国建筑工业出版社,1998..
  • 3张富成.上海大剧院空调设计.暖通空调新技术1[M].北京:中国建筑工业出版社,1999.125—128.
  • 4Busweiler U. Air conditioning with a combination of radiant cooling, displacement ventilation, and desiccant cooling. In:ASHRAE Trans. 1993, 99. 503- 510.
  • 5Brunk M F. Cooling ceiling ceilings--an opportunity to reduce energy costs by way of radiant cooling. In: ASHRAE Trans.1993.99. 479-487.
  • 6Martin Behne. Indoor air quality in rooms with cooled ceilings.Mixing ventilation or rather displacement ventilat on? Energy Buildings, 1999,30:155 - 166.

二级参考文献1

共引文献44

同被引文献200

引证文献38

二级引证文献216

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部