针对鹤岗发电有限责任公司生活污水处理站鼓风曝气方式存在的问题,分析了污水处理站曝气溶氧的方式及机理,通过实验证明该生活污水处理站罗茨风机采用每间隔4h运行30min的运行方式可满足运行要求,节约电能。
In order to solve the existing problems with the air blast modes at the waste water treatment plant of He-gang Power Generation Co. , Ltd, the mode and mechanism of oxygen dissolution in air blast at the waste water treatment plant is discussed. Experimental results show that the operating requirement can be satisfied by operating the blower fan for 30minutes in every 4 hours, and electric energy can be saved.
出处
《黑龙江电力》
CAS
2003年第4期313-315,共3页
Heilongjiang Electric Power
关键词
污水处理
溶解氧
鼓风曝气
试验
运行方式
waste water treatment
dissolution of oxygen
air blast
test
operating mode