分析和研究复合绝缘子湿工频电气试验方法表明 ,现有 GB和 JB标准所规定的湿工频电气试验方法并不能反映复合绝缘子最严酷的运行条件。为此提出了增加自来水浸泡 96 h的预处理程序的新试验方法 。
This paper studies the wet electrical test method of composite insulators. The results show that the wet electrical methods according to GB and JB standard can not simulate the most inclement operation conditions. A method of wet electrical test which can simulate the most inclement operation conditions of the composite insulators is presented. The results show that there is much difference between two test methods.
出处
《高电压技术》
EI
CAS
CSCD
北大核心
2003年第8期45-46,共2页
High Voltage Engineering