摘要 建立了一种基于溶液电导率的监测来快速评定阻垢剂性能的方法。在相同水体的条件下,通过对溶液电导率的测定,比较有阻垢剂和无阻垢剂时溶液的过饱和度,找出阻垢剂的最佳投加浓度。 A accurate and rapid evaluation method of scale inhibitors has been developed and tested. This method is based on solution conductivity measurement. In the given water conditions, we can compare supersaturation of the solutions in the presence of a special amount of scale inhibitor with the solutions without scale inhibitor. The efficiency of the scale inhibitors is evaluated by this method. We can determine the stabilizing property of the scale inhibitor at optimum concentration.
出处 《工业水处理》 CAS CSCD 2003年第8期29-32,共4页 Industrial Water Treatment
关键词 溶液电导率 评定 阻垢剂 性能 监测 过饱和度 工业循环冷却水 结垢 scale inhibitor conductivity supersaturation evaluation
  • 相关文献

参考文献4

  • 1中国石油化工总公司.冷却水分析和试验方法[M].北京:石油出版社,1989..
  • 2.HG/12024—1991.水处理药剂阻垢性能的测定方法—鼓泡法[S].,1991..
  • 3盛骤 谢式千.线性代数与数理统计[M].杭州:浙江大学出版社,1993.228-229.
  • 4Drela I, Flaewica P, Kuczwsa S. New rapid test for evaluate of scale inhibitors[J]. Water Research, 1998,32(10) :3 188 -3 191.