期刊文献+

计及静态安全约束的跨区域双边交易最大交易量实用计算方法 被引量:11

A PRACTICAL METHOD FOR CALCULATING MAXIMUM TRANSACTION VOLUME OF BILATERAL TRANSACTION IN MULTIREGIONAL ELECTRICITY MARKET CONSIDERING STATIC SECURITY CONSTRAINTS
下载PDF
导出
摘要 提出了基于直流潮流分布因子的区域电网之间双边交易最大交易量的快速计算方法。该方法考虑了线路热稳定、区域间联络线割集潮流的动稳定约束和计及“N-1斁蔡踩际8梅椒墒视糜谇蚰诤颓蚣涞慵缘慵淖畲蠼灰琢康募扑恪EEE 30节点系统的计算结果验证了该方法的快速性与有效性。 For the multirigional electricity market which will be soon actualized in China, a practical and fast method, which is based on the DC power flow linear distribution factors, to calculate the maximum transaction volume between two regions in a multiregional power system is presented. Considering the thermal stability of transmission lines and the dynamic stability constraint for cut set power flow of tie-line between regions as well as the N-1 static security constraint, this method can be applied to the calculation of maximum transaction volume between two bus sets in a same region as well as that between two bus sets in two different regions. The calculation results for IEEE-30 bus system show that the presented method is fast and effective.
出处 《电网技术》 EI CSCD 北大核心 2003年第9期1-5,共5页 Power System Technology
基金 国家重点基础研究专项经费资助项目(G1998020305) 香港政府研究基金(RGC) 香港大学研究基金(CRCG)资助项目
关键词 电力系统 电网 潮流计算 静态安全约束 双边交易 最大交易量 快速计算方法 Regional electricity market Bilateral transaction Available transfer capability (ATC) DC power flow linear distribution factor Static security constraints Power system
  • 相关文献

参考文献10

  • 1Federal Energy Regulatory Commission. Open access same-time information system and standards of conduct[Z]. Docket No. RM 95-9-000, Order 889, April 1996.
  • 2North American Electric Reliability Council. Available transfer capability definitions and determination[Z]. A Reference Document Prepared by TTC Task Force, June 1996.
  • 3Ejebe O C, Waight J G, Santos-Nieto Met al. Fast calculation of linear available transfer capabillty[J]. IEEE Transactions on Power Systems, 2000, 15(3): 1112-1116.
  • 4Saner PW, Reinhard K E, Overbye T J. Extended factors for linear contingency analysis[A]. Proceedings of the 34th Hawaii International Conference on System Sciences[C], Maui, Hawaii, 2001 : 697-703.
  • 5Eans M K, Quada J J, Sackett B. Fast linear contingency analysis[J]. IEEE Transactions on Power Apparatus and Systems,1982, PAS-101(4): 783-791.
  • 6Gravener M H, Nwankpa C, Tai-Sim Y. ATC computational issues[A]. Proceedings of the 32nd Annual Hawaii International Conference, Maui, Hawaii, 1999.
  • 7Shaaban M, Ni YLxin, Wu F F. Available transfer capability evaluation by decomposition[A]. Power Engineering Society Summer Meeting[C], 2001: 1122-1126.
  • 8Tuglie E D, Dicorato M, Scala M L et al, A static Optimization approach to assess dynamic available transfer capability[J]. IEEE Transactions on Power Systems, 2000, 15(3): 1069-1076.
  • 9Greene S, Dobson I, Alvarado F L. Sensitivity of transfer capability margins with a fast formula[J]. IEEE Transactions on Power Systems, 2002, 17(1): 34-40.
  • 10Wood A J, Wollenberg B F. Power generation operation, and control[M]. New York: John Wiley & Sons, inc Second edilion, 1996.