期刊文献+

转子角测量装置的优化配置 被引量:5

OPTIMAL PLACEMENT OF ROTOR ANGLE TRANSDUCERS
下载PDF
导出
摘要 结合同调分群与基于信息含量的方法,提出了一种转子角测量装置的优化配置方法。以发电机转子角响应的信息含量为性能指标,通过系统聚类分析将动态场景集压缩;同调分群并结合电气距离形成配置地点的候选集合;以Gramian行列式作为信息含量的表征,采用Tabu搜索算法从候选集合中有效地求得最优解或次优解。实际系统的仿真结果表明了这种配置方法的合理性和有效性。 Combining coherency identification with infor-mation content, an optimal placement method of rotor angle transducers is proposed in this paper. Based on generator rotor angle responses, raw dynamic scenario set is compressed through hierarchical clustering analysis. Incorporating coheren-cy identification with electrical distance measure, placement candidates are formed for each scenario of the compressed set. Using Gramian determinant as the information content measure, a tabu search algorithm is implemented to find the optimal or nearly optimal placement sites from the candidates. Simulation results of an actual power system demonstrate its rationality and effectiveness.
出处 《中国电机工程学报》 EI CSCD 北大核心 2003年第9期132-136,共5页 Proceedings of the CSEE
基金 国家电力公司基金项目(SP11-2001-04-50-09)
关键词 电力系统 运行方式 转子角测量装置 优化配置 Power system stability Rotor angle Optimal placement Information content
  • 相关文献

参考文献8

  • 1刘玉田,林飞.基于相量测量技术和模糊径向基网络的暂态稳定性预测[J].中国电机工程学报,2000,20(2):19-23. 被引量:79
  • 2Baldwin TL, MiliL, Boisen M B, et al. Power system observability with minimal phasor neasurement placement[J]. IEEE Transactions on Power Systems, 1993, 8(2): 707-715.
  • 3Ota Y, Ukai H, Naksmura K, et al. Evaluation of stability and electric power quality in power system by using phasor measurements[C]. Proceedings of Intemational Conference on Power System Technology, Australia, December 2000.
  • 4Kamwa I, Grondin R. PMU coafigeuration for system dynamic performance measurement in large multiarea power systems[J].IEEE Transactions on Power Systems, 2002, 17(2): 385-394.
  • 5Wehenkel L. A statistical spproach to the identification of electrical regions in power systems [C]. Proceedings of Stockbolm Power Tech Conference, Sweden, June 1995.
  • 6SAS Institute Inc. SAS/STAT User's Guide, Version 8[Z]. Cary, NC:SAS Institute Inc, 2000.
  • 7Sadesh P,Spall J C.Optimal sensor configaration for complex systems[C]. Proceedings of the American Control Confereace, USA, June 1998.
  • 8Kincaid R K, Padula S L. D-optimal designs for sensor and actuator locations[J].Computers & Operations Research, 2002, 29(6): 701-713.