摘要
分析了某大型油库泡沫站泡沫液失效的问题,找出了泡沫液失效的主要原因是止回阀关闭不严导致消防水反串进入泡沫液罐,提出并对止回阀更换为电动阀的整改措施。
Failure of AFFF liquid was analyzed.The reason of it was that the valve was not so tight that the fire fighting water was leaked into the tank.The measure was put forward to replace the check valve with the motor operated valve.
出处
《石化技术》
CAS
2015年第1期32-,共1页
Petrochemical Industry Technology
关键词
水成膜泡沫液
失效分析
整改措施
AFFF liquid,failure analysis,rectification measures